Telephone:0086-592-3193333
NOTICE:
Advanced production equipment, diverse product types, sufficient supply, and fast delivery
Vibration sensor
Current Location: HOME > PRODUCTS > Vibration sensor
KR-939SB3 Three-Parameter Vibration Probe

1  Product Overview

The KR-939SB3 is an integrated three-parameter combination probe that measures lubricating oil temperature, lubricating oil level and casing vibration of cooling tower fan gearboxes. It is a non-bus, universal combination probe in the KR-939 series of fan safety monitoring systems. The probe can be connected directly to a KR-939B3 Fan Safety Monitor for stand-alone machine protection, or used with general-purpose secondary instruments and computerised data acquisition and control systems such as DCS and PLC.

The sensing, conversion and transmission circuits for all three parameters are integrated in a single probe body, which outputs three independent 4–20 mA standard current signals, one for each safety parameter. The probe can therefore be wired directly into any standard analogue input channel.

Temperature is measured with a semiconductor integrated sensor; oil level is measured on the thermal-conductivity sensing principle; vibration velocity is measured with a magnetoelectric sensor that acquires the velocity signal of the mechanical vibration directly. The vibration signal is processed by an amplifier, a band-pass filter and a true-RMS converter, so that the complex vibration waveform within the effective bandwidth is converted into a true root-mean-square value; a voltage/current drive stage finally produces the 4–20 mA output.

The probe is a compact, one-piece, all-stainless-steel and corrosion-resistant unit. Its long-line, interference-resistant current transmission, together with its sealing, shock resistance and explosion-proof provisions, allow continuous on-line operation in harsh measurement environments. Because it acquires the parameters most closely related to the safe operation of the monitored machine at a single point, the probe is equally suitable for direct safety monitoring of other rotating and reciprocating machinery, and is a standard vibration safety monitoring unit for modern industry, national defence and scientific research.

2  Key Features

  • Three measurements in one device: oil temperature, oil level and vibration velocity, from a single mounting point and a single cable run.
  • Three independent 4–20 mA current outputs (T = temperature, A = vibration, L = oil level) for direct connection to DCS, PLC or panel instruments.
  • Direct connection to the KR-939B3 Fan Safety Monitor for single-machine protection.
  • Magnetoelectric vibration sensing with band-pass filtering and true-RMS conversion, 10–1000 Hz measurement bandwidth.
  • Thermal-conductivity oil level measurement referenced to the normal oil level of the gearbox.
  • Fully stainless-steel, fully enclosed, waterproof and corrosion-resistant housing, weighing approximately 0.6 kg.
  • Long-line anti-interference current transmission with built-in supply reverse-polarity protection.
  • Explosion-proof versions available for explosive gas atmospheres (e.g. Exd IIB T4).
  • Thread specification and probe-rod insertion depth configurable to order.

3  Typical Applications

  • Cooling tower fan gearboxes: simultaneous monitoring of lubricating oil temperature, lubricating oil level and casing vibration.
  • Single-machine fan protection where the probe is connected to a KR-939B3 Fan Safety Monitor.
  • Plant-wide condition monitoring where the three 4–20 mA signals are wired to DCS or PLC analogue input modules.
  • Direct safety monitoring of other rotating machinery and reciprocating machinery.

4  Appearance and Installation

The KR-939SB3 is a stainless-steel, fully enclosed and waterproof structure weighing approximately 0.6 kg. The probe is installed by means of its external thread into the threaded mounting hole on the casing of the fan gearbox; the probe rod is inserted into the gearbox, where it acquires the lubricating oil temperature, the lubricating oil level and the casing vibration signals, and completes the transmission output.

The thread specification and the insertion depth of the probe rod must be stated at the time of ordering. The external structure of the probe is shown in Figure 1.

Three-Parameter Vibration Probe

5  Technical Specifications

Table 1   Measuring ranges and accuracy

ParameterMeasuring rangeAccuracySensor / remarks
Oil temperature0 to 100 °C±1 °CSemiconductor integrated sensor
Oil level−10 to +40 mm±5 mmThermal-conductivity sensing; 0 mm is the lower limit of the normal gearbox oil level; the measured medium must be a non-conductive medium
Vibration velocity0 to 20 mm/s±1 mm/sMagnetoelectric sensor; output proportional to the true RMS of vibration velocity; frequency range 10–1000 Hz

Table 2   Electrical, environmental and mechanical data

ItemSpecification
Output signalThree independent 4–20 mA DC active current outputs (T = temperature, A = vibration, L = oil level); passive resistive load required
Maximum load resistanceRmax = (V − 15) / 0.02 Ω, where V is the supply voltage; the value includes the internal resistance of the cable
Supply voltageDC 24 V ± 2 V
No-load operating voltageDC 18 V
Maximum protection voltageDC 30 V
Rated currentDC 80 mA
Maximum instantaneous current150 mA
Supply protectionBuilt-in voltage reverse-polarity protection
Electrical connection5-wire, 6-terminal
Warm-up timeApprox. 2 min stable preheating after power-on
Response (damping) timeApprox. 1 min
Ambient temperature−20 to +80 °C
Ambient humidity0 to 100 % RH (cable ports sealed with 704 silicone rubber)
HousingStainless steel, fully enclosed, waterproof, corrosion-resistant
WeightApprox. 0.6 kg
MountingExternal thread into the gearbox casing; probe rod inserted into the gearbox
Explosion-proof versionAvailable to order, e.g. Exd IIB T4; the housing earth terminal must be reliably grounded

6  Electrical Connection

The probe uses a 5-wire, 6-terminal connection. Terminal assignment and conductor colours of the pre-assembled cable are given in Table 3; the wiring principle is shown in Figure 2.

Table 3   Terminal assignment and conductor colours

TerminalMarkingFunctionConductor colour
1+V+24 V DC power supplyBrown
2GConnected to the housing; may be used for the cable shieldShield / drain wire
3-VCommon ground (0 V)Red
4TOil temperature signal output, 4–20 mAYellow
5AVibration signal output, 4–20 mABlue
6LOil level signal output, 4–20 mABlack

Note  The probe is supplied with a pre-assembled five-core shielded cable, and the conductor colours correspond to the terminals listed in Table 3. Typical wiring is shown in Figure 2.

KR-939SB3 Three-Parameter Vibration Probe(pic2)

7  Cable, Installation and Maintenance

Recommended cable: 5 × 0.3 mm² RVVP five-core shielded cable, with a cable gland sealing diameter of 6–7 mm. Owing to the high humidity inside the fan stack, the cable entry must be sealed thoroughly with silicone rubber. It is recommended that a pre-assembled cable of 10–15 m be ordered together with the probe, so that the cable can be led out to a terminal box outside the stack for connection.

Long-term operation or heavily contaminated lubricating oil will cause an error in oil level measurement. In this case, remove the probe and dip the probe rod repeatedly in a non-aqueous organic solvent to clean off the oil deposits; normal measurement is then restored.

Mark up as-built drawings once installation is complete.

8  Explosion-Proof Version

For explosive gas atmospheres, explosion-proof versions with the corresponding explosion protection class can be supplied, for example Exd IIB T4. The housing earth terminal of an explosion-proof probe must be reliably grounded.

9  Ordering Information

When ordering, please state the following:

  • Model: KR-939SB3, or the explosion-proof version with the required protection class.
  • Thread specification of the mounting hole on the gearbox.
  • Insertion depth of the probe rod.
  • Length of the pre-assembled shielded cable (e.g. 10 m or 15 m).
  • Model or structure of the monitored equipment, where selection assistance is required.